HLR Series Air to Water Heat Pump | SPECIFICATIONS

Model |
HLR8WZ Na-M |
HLR10WZ Na-M |
HLR12,5WZ Na-M |
HLR15WZ Na-M |
HLR22SNa-M |
HLR25SNa-M |
HLR35SNa-M |
HLR45SNa-M |
Rated Capacity |
Cooling |
kW |
7.5 |
10 |
12.5 |
14.2 |
21.5 |
22.8 |
31 |
42 |
Heating |
kW |
9 |
12 |
13 |
16.5 |
25 |
25 |
37.5 |
49 |
Capacity steps |
% |
0% - 100% |
0% - 50% - 100% |
EER - ESEER |
W / W |
2,1 - 3,05 |
2,2 - 2,79 |
2,2 - 3,05 |
2,5 - 3,05 |
2,5 - 3,33 |
2,6 - 3,41 |
2,6 - 3,44 |
2,3 - 3,05 |
COP |
W / W |
2.7 |
2.7 |
2.7 |
3.1 |
2.9 |
2.8 |
3 |
2.8 |
Power supply |
380 ~ 415V - 3N - 50Hz |
Power Input |
Cooling |
kW / Αmp |
3,5 / 6,65 |
4,4 / 8,35 |
5,7 / 10,8 |
5,7 / 10,8 |
8,6 / 17,4 |
8,8 / 17,8 |
11,9 / 25,1 |
18,3 / 39,7 |
Heating |
kW / Αmp |
3,3 / 6,26 |
4,4 / 8,35 |
4,8 / 9,11 |
5,3 / 10,0 |
8,6 / 17,4 |
8,9 / 18,0 |
12,5 / 26,3 |
17,5 / 38 |
Max Power Input |
Cooling |
kW / Αmp |
5 / 9,4 |
6,7 / 13 |
7,2 / 13,5 |
7,5 / 14,5 |
12,5 / 21,9 |
13,5 / 23,4 |
14,5 / 28,3 |
22 / 42,4 |
Heating |
kW / Αmp |
4 / 7,4 |
5,1 / 8,6 |
6,2 / 13,7 |
6,8 / 13 |
12 / 21,6 |
12 / 21,6 |
14,5 / 28 |
22 / 44 |
Safeties |
Relief Valve, Air Vent. |
Relief Valve, Air Vent. |
Refrigerant |
Type |
R - 410A |
Water Flow Volume |
l/s |
0.38 |
0.48 |
0.59 |
0.72 |
1.05 |
1.2 |
1.4 |
2.2 |
Water Pump |
Delivery Lift |
mH2O |
18 |
18 |
18 |
18 |
22 |
24 |
25 |
27 |
Power Input |
kW |
0.55 |
0.55 |
0.55 |
0.55 |
0.75 |
0.75 |
1.5 |
1.5 |
Expansion Tank |
L |
5 |
5 |
5 |
5 |
8 |
8 |
8 |
8 |
Chilled Water Outlet/Inlet |
inch |
1" |
1" |
1" |
1" |
1" |
1" |
1" |
1-1/2" |
Evaporator |
Type |
Tube in tube |
Tube in tube |
Tube in tube |
Tube in tube |
Tube in tube |
Tube in tube |
Shell and tube |
Shell and tube |
Compressor |
Type / Quantity |
Scroll / 1 |
Scroll / 2 |
Power Input |
RLA(A) |
6.58 |
8.2 |
9.8 |
9.8 |
8.61 |
8.22 |
13.6 |
19.2 |
Condenser |
Type |
Aluminum fin-copper tube |
Fan |
Type / Quantity |
Axial / 1 |
Axial / 2 |
Power Input |
kW |
0,092 x 1 |
0,068 x 2 |
0,092 x 2 |
0,092 x 2 |
0,4 x 2 |
0,4 x 2 |
0,6 x 2 |
0,8 x 2 |
Sound pressure level |
dB(A) |
60 |
60 |
60 |
60 |
66 |
66 |
68 |
68 |
Dimensions (W x D x H) |
Indoor |
mm |
950 x 412 x 840 |
950 x 412 x 1250 |
950 x 412 x 1250 |
950 x 412 x 1250 |
1460 x 530 x 1850 |
1460 x 530 x 1850 |
1750 x 800 x 1760 |
1750 x 800 x 1760 |
Outdoor |
mm |
1100 x 450 x 288 |
1100 x 450 x 288 |
1100 x 450 x 288 |
1100 x 450 x 288 |
|
|
|
|
Net Weight |
Indoor/Outdoor |
kg |
90,0 / 84,0 |
112,0 / 84,0 |
115,0 / 84,0 |
123,0 / 84,0 |
370.0 |
390.0 |
680.0 |
755.0 |
Operation Range |
οC |
Cooling: OutTemp. 16~48 DB ℃, water 7~12, Heating: OutTemp.-15~28 DB ℃, water 40~45 |
Units capacity and power input are based in the following conditions:
Cooling: Water 7οC, ΔΤ= 5οC, OutTemp. 35οC DB/24oC WB
Heating: Water 45οC, ΔΤ= 5οC, OutTemp. 7οC DB/6oC WB
This series of compact mini heat pump, ranging from 8 to 45 kW is the ideal solution for small and medium household and light commercial applications. All units come complete with a hydronic assembly and can be installed as a split system for capacities from 8 to 15 kW and a compact modular type from 22 to 45 kW. It incorporates a water pump, flow switch, expansion vessel, water replenishment and safety valve.
Convenient Installation
Easy to install versatile split type hydronic assembly for 8 to 15 kW units allow indoor installation for low temperature anti freeze protection. Compact units from 22 to 45 kW enjoy a special designed air outflow in 45 degrees allowing installation in a limited space.
Compressor
High end Scroll compressors built into a carefully designed refrigerating circuit allows big capacity increased energy efficiency, certified by Eurovent. The unit is able to control an auxiliary heating source, such as an electric heater, petrol or gas burner, during low ambient temperature operation.
Quiet Operation
Redesigned low noise fan motor and fan blade, together with a high end water pump along with other noise reduction techniques, built into the design, allow a low overall operation noise level.
Control